Voltage type for actuating |
AC/DC |
Rated control supply voltage at AC 50 Hz |
100 V |
Rated control supply voltage at AC 60 Hz |
100 V |
Rated control supply voltage at DC |
100 V |
Type of electrical connection of main circuit |
Screw connection |
Rated impulse voltage withstand (Uimp) |
8 kV |
Operating time, closing delay |
42 ms |
Operating time, opening delay |
17 ms |
Optional overload relays |
Electronic |
Rated isolation voltage (Ui) |
600V per UL, CSA |
Function |
Non-reversing contactor |
Standard coil, pick-up |
40VA/40 W @ 100…250V AC/DC |
Standard coil, hold-in |
4VA/2 W @ 100…250V AC/DC |
General purpose current (enclosed) |
80 A @ 600V per UL/CSA |
FLA |
115 A @ 600V, 3-phase per UL/CSA HVAC applications |
Rated operational current and power (enclosed) |
92 A @ 200-208V, 3-phase per UL/CSA |
LRA |
690 A @ 440-480V AC, 3-phase per UL/CSA HVAC applications |
Electromagnetic compatibility |
IEC 60947-1 – Environment A and B (100-E09…E38 only.) |
Operating limits, dropout |
(≤0.60) x Us @ DC control |
Rating for switching AC motors |
3-poles: 75 Hp @ 575V, AC-2, AC-3 (60 Hz) |
Operating limits, pick-up |
(0.85…1.1) x Us @ 50/60 Hz |
MCCB current rating |
Type 2 (per IEC 60947-4-1): 880 A @ 400 V, 70 kA available fault current |
DIN fuses (gG) current rating |
Type 2 (per IEC 60947-4-1): 160 A @ 400 V, 100 kA available fault current |
Rated voltage (Ue) |
24V, 48V, 110V, 220V, 440V DC |
Rated operational current and power |
56 A @ 115V AC, 500000 electrical operations, 1-phase per UL/CSA elevator duty |
Coil voltage |
100 to 250V AC/DC |
Switching of lighting loads |
Tungsten lamps: 115 A @ 600V, 3-phase (break all lines) per UL/CSA |
UL class RK5 fuses rating |
Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 200 A @ 600V, 10 kA available fault current |
Rated operational current (Ie) |
96 A @ 440V, AC-2, AC-3 switching of 3-phase motors (50 Hz), ambient temperature 60 °C (140 °F) |
UL class J and CSA HRCI-J fuses rating |
Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 200 A @ 600V, 100 kA available fault current |
UL inverse-time circuit breaker |
Type 1 Combination (per UL 60947 and CSA 22.2 No. 14): 250 A @ 600V, 50 kA available fault current |
Switching of power transformers |
Apparent power: 87 kVA @ 480V, 60 Hz (n = 20) |
Rated operational power (Pe) |
93 kW @ 415V, AC-1 active power load (50/60 Hz), ambient temperature 40 °C (104 °F) |
Switching of DC loads |
3-poles in series: 130 A @ 220V (Shunt-wound motors starting, reverse current breaking, reversing, stepping DC-3 at 60 °C) |
Optional accessories |
Side-or front-mount auxiliary contacts, Mechanical interlocks, IP20 terminal shields, Connecting bars |
Features |
Panel mounting or mounting on 35 mm DIN rail, AC/DC electronic coil, Made of environmentally friendly materials |