Voltage type for actuating |
DC |
Rated control supply voltage at AC 50 Hz |
0 V |
Rated control supply voltage at AC 60 Hz |
0 V |
Rated control supply voltage at DC |
24 V |
Current (Ie), max |
16 A |
Switching frequency, max |
220 ops/h |
Main current circuit resistance |
2.7 mohm |
Cross section per UL/CSA |
16 |
Rated operational current for contactor at elevator duty (UL/CSA) |
5Hp @ 230V |
Rated isolation voltage (Ui) |
690V @ IEC |
Rated voltage (Ue) |
690V @ AC, 50/60 Hz |
Rated operational power for contactor at wye-delta |
7.5Hp @ 200V, 60 Hz |
Rated filament current |
18A @ 230/240V, AC-5b |
Power dissipation |
2.1 W @ 400V, AC-3, Ie |
Coil terminal conductor cross section |
1…4 mm² @ 2 conductor |
Rated current (enclosed) |
17.5A @ 200V, 3-phase per UL/CSA |
Rated power (enclosed) |
5Hp @ 230V, 3-phase per UL/CSA |
Coil consumption pick-up (avg/peak) |
14/22 W @ DC (electronic-EA) |
General purpose current (enclosed) |
30 A per UL/CSA |
Capacitance, max |
500 µF @ short-circuit current of 20 kA |
Switching of low inductive loads |
32A @ 440V, AC-7a per IEC 61095 (50 Hz) |
Operating limits, pick-up |
(0.85…1.1) x Us @ 50 Hz, 60 Hz, 50/60 Hz |
Switching of motor load |
19A @ 230V, AC-7b per IEC 61095 (50 Hz) |
Short time withstand (Icw) |
170A @ 10s, 60 °C |
Coil consumption, hold-in |
9.5VA/2.7 W @ 50 Hz, 60 Hz, 50/60 Hz |
Coil consumption, pick-up |
75VA @ 50 Hz, 60 Hz, 50/60 Hz |
Operating time |
20…50 ms @ DC (electronic) opening delay |
Total power dissipation |
DC control (electronic): 3.8 W @ 400V, AC-3, Ie |
Operating limits, dropout |
(0.3…0.6) x Us @ 50 Hz, 60 Hz, 50/60 Hz |
Switching of lamps |
Gas discharge lA, open: 28A @ 40°C, AC-5a |
Switching of hermetically sealed cooling compressor motors |
9.3A @ 690V, AC-8b (manual reset of overload release (50 Hz)) |
Coil insulation class |
Class F per IEC 60085, UL Class 105 |
Rating for switching AC motors |
7.5 kW @ 690V @ 50Hz, 3-phase (AC-2, AC-3, AC-4) |
BS88 fuses current rating |
Type 2 (per IEC 60947-4-1): 32A @ 415V, 65 kA available fault current |
UL class K5 and RK5 fuses rating |
70A @ 600V, 5 kA available fault current per UL 508 and CSA 22.2 No. 14 |
UL class CC and CSA HRCI-MISC fuses rating |
30A @ 100kA available fault current per UL 508 and CSA 22.2 No. 14 |
UL inverse-time circuit breaker |
50A @ 480V, 5 kA available fault current per UL 508 and CSA 22.2 No. 14 |
Coil voltage |
24V DC electronic coil |
Rated operational current (Ie) |
9A @ 690V, AC-4 (approximately 200000 ops) |
Rated operational power (Pe) |
7.5 kW @ 690V, AC-4 (approximately 200000 ops) |
DIN fuses (gG, gL) current rating |
Type 2 (per IEC 60947-4-1): 35A @ 690V, 50 kA available fault current |
UL class J and CSA HRCI-J fuses rating |
30A @ 100kA available fault current per UL 508 and CSA 22.2 No. 14 |
Switching of power transformers |
Apparent power: 9.4 kVA @ 500V, AC-6a @ 50Hz (n = 30) |
Switching of 3-phase Capacitors |
Single capacitor: 8.5 kVAR @ 240V, AC-6b, 50 Hz, 60 °C (inductance of leads between capacitors in parallel: minimum 6 µH) |
Switching of DC loads |
3-pole:32A @ 110V (Non-inductive or slightly inductive loads or resistance furnaces DC-1 at 60 °C) |
Contacts |
3 main poles with NC mechanically linked or mirror ftdback contacts |
Function |
Reversing contactor |
Rated impulse voltage withstand (Uimp) |
6 kV |
Conventional coil type |
True |
Electronic-EI coil type |
True |
Rated coil frequency |
AC 50/60 Hz, DC |
Ripple, max |
±15% @ DC (electronic) |
OFF time, min |
50 ms @ DC (electronic) |