Inicio/Others/140M-F8E-C10, Motor Protection Circuit-Breaker
140M-F8E-C10, Motor Protection Circuit-Breaker
USD $585.88 - (IVA Incluido) + Envío
Sin existencias
Motor Protection Circuit-Breaker
Adj. Thermal Current Range (A) |
6.3 – 10A,MxRtg MCPs(no OvPrt)is 1200.0A |
With integrated auxiliary switch |
False |
With integrated under voltage release |
False |
Rated short-circuit breaking capacity lcu at 400 V, AC |
100 kA |
Rated operation power at AC-3, 400 V |
4 kw |
Rated permanent current Iu |
10 A |
Rated operation power at AC-3, 230 V |
2.2 kw |
Rated operating voltage |
230 A |
Type of control element |
Turn button |
Overload release current setting |
6.3 A |
Type of electrical connection of main circuit |
Screw connection |
Magnetic release current per IEC |
130 A |
Magnetic trip current, nom |
130 A |
Rated operational current (Ie) per IEC |
10 A |
Rated supply current (Ie) |
6.3 A |
Short circuit current (Icu) for group motor installation, max |
65kA @ 480V |
Short circuit current (Type 2 coordination) with 100-C IEC contactor, max |
65kA @ 480V |
Current range |
6.3…10 A |
Ultimate short circuit breaking capacity (Icu) per IEC |
65kA @ 440/460V AC |
Rated service short circuit breaking capacity (Ics) per IEC |
50kA @ 500/525V AC |
Insulation voltage (Ui) |
Rated 690V per IEC |
Hp rating, max |
7.5Hp @ 575V, 3-phase |
Electrical life cycle |
30000 ops (Ie maximum) |
Short circuit current for self-protected combination motor controller with 100-C contactor, max |
65 kA @ 480Y/277V, UL 508-Type E |
Switching of standard motors per IEC |
7.5 kW @ 690V (AC-3), 3-phase |
KW rating, max |
7.5 kW @ 690V (AC-3), 3-phase |
Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC |
No back-up fuse required @ 230/240V AC |
Short circuit current for combination motor controller with 100-C IEC contactor, max |
65 kA @ 480Y/277V, UL 60947-4-1-Type F |
Total power loss (Pv) for circuit breaker |
7…22 W @ rated load/operating temperature |
Short circuit current for group motor installation with 100-C IEC contactor, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Short circuit current for motor disconnect with 100-C IEC contactor, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Rated thermal current (Ith) |
6.3…45 A up to 60 °C (140 °F) ambient temperature |
Short circuit current for tap conductor protection, max |
65 kA @ 480Y/277V, UL 60947-4-1-manual motor controller |
Short circuit current for combination motor controller, max |
65kA @ 480V/277V, UL 60947-4-1 self-protected (Type E) |
Fuse or circuit breaker per NEC, max |
600 A, UL 60947-4-1-manual motor controller |
Rated impulse withstand voltage (Uimp) |
Main circuits (Uimp)/overvoltage category: 6 kV/III, 8 kV (disconnect) |
Short circuit current for group motor installation, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Short circuit current for motor disconnect, max |
65kA @ 480V, UL 60947-4-1-manual motor controller |
Number of poles |
3 |
With thermal protection |
True |
Phase failure sensitive |
True |
Switch off technique |
Thermomagnetic |
Switching frequency, max |
25 ops/h |
Trip class |
10 |
Rated frequency |
45 Hz |
Phase loss protection |
Differential release |
Fuse or circuit breaker rating with 100-C IEC contactor per NEC, max |
600 A, UL 60947-4-1-manual motor controller |
Width |
54 mm |
Depth |
110 mm |
Height |
111.4 mm |
Contactor size (Type 2 coordination) with 100-C IEC contactor, min |
100-C30 @ 600V |
Frame size |
Frame size F, 45 A |
Contactor size, min |
100-C30, UL-508 -Type E self-protected combination motor controller |
Device construction |
Built-in device fixed built-in technique |
Degree of protection (IP) |
IP2X |
Weight |
782 lb |
Mechanical life operations |
30000 /h |
Breaking capacity |
High breaking capacity |
Shock |
Transport (60068-2-27): 30 G/11 ms, OFF |
Protection type |
Adjustable thermal/fixed magnetic (13 x In) |
Factory option |
No circuit-breaker auxiliary or trip contacts |
Vibration |
Ops (60068-2-6): 5 G |
Ambient storage temperature |
-40 °C |
Ambient operating temperature |
-25 °C |
Ambient temperature compensation |
-25 °C |
Site altitude |
To 2000 m N.N. (6561 ft) |
Dependence on temperature |
No reduction @ 60 °C (140 °F) |
Magnetic release current (±20 %) |
Fixed setting: 18…22 x Ie maximum (Ie maximum = maximum values of setting ranges) for T version |
Pollution degree |
3 |
Climatic resistance |
Operating humidity/moisture heat (60068-2-3): 5…95% non-condensing |
Utilization category |
Motor starter: AC-3 (IEC60947-4-1) |
Overload protection characteristics |
IEC 60947-4-1 motor protection |
Marca
Rockwell Automation
Product has been added to your cart
There are no reviews yet.