| Adj. Thermal Current Range (A) | 32 – 45A,MxRtg MCPs(no OvPrt)is 1200.0A |
|---|---|
| Circuit Breaker Type | Mtr Prt Circuit Breaker |
| With integrated auxiliary switch | False |
|---|---|
| With integrated under voltage release | False |
| Rated short-circuit breaking capacity lcu at 400 V, AC | 65 kA |
| Rated operation power at AC-3, 400 V | 22 kw |
| Rated permanent current Iu | 45 A |
| Rated operation power at AC-3, 230 V | 13 kw |
| Rated operating voltage | 230 A |
| Type of control element | Turn button |
| Overload release current setting | 32 A |
| Type of electrical connection of main circuit | Screw connection |
| Magnetic release current per IEC | 585 A |
| Magnetic trip current, nom | 585 A |
| Rated operational current (Ie) per IEC | 45 A |
| Rated supply current (Ie) | 6.3 A |
| Short circuit current (Icu) for group motor installation, max | 65kA @ 480V |
| Short circuit current (Type 2 coordination) with 100-C IEC contactor, max | 65kA @ 480V |
| Current range | 32…45 A |
| Ultimate short circuit breaking capacity (Icu) per IEC | 65kA @ 400/415V AC |
| Rated service short circuit breaking capacity (Ics) per IEC | 6kA @ 690V AC |
| Insulation voltage (Ui) | Rated 690V per IEC |
| Hp rating, max | 40Hp @ 575V, 3-phase |
| Electrical life cycle | 30000 ops (Ie maximum) |
| Short circuit current for self-protected combination motor controller with 100-C contactor, max | 65 kA @ 480Y/277V, UL 508-Type E |
| Switching of standard motors per IEC | 40 kW @ 690V (AC-3), 3-phase |
| KW rating, max | 40 kW @ 690V (AC-3), 3-phase |
| Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC | No back-up fuse required @ 230/240V AC |
| Short circuit current for combination motor controller with 100-C IEC contactor, max | 65 kA @ 480Y/277V, UL 60947-4-1-Type F |
| Total power loss (Pv) for circuit breaker | 7…22 W @ rated load/operating temperature |
| Short circuit current for group motor installation with 100-C IEC contactor, max | 65kA @ 480V, UL 60947-4-1-manual motor controller |
| Short circuit current for motor disconnect with 100-C IEC contactor, max | 65kA @ 480V, UL 60947-4-1-manual motor controller |
| Rated thermal current (Ith) | 6.3…45 A up to 60 °C (140 °F) ambient temperature |
| Short circuit current for tap conductor protection, max | 65 kA @ 480Y/277V, UL 60947-4-1-manual motor controller |
| Short circuit current for combination motor controller, max | 65kA @ 480V/277V, UL 60947-4-1 self-protected (Type E) |
| Fuse or circuit breaker per NEC, max | 600 A, UL 60947-4-1-manual motor controller |
| Rated impulse withstand voltage (Uimp) | Main circuits (Uimp)/overvoltage category: 6 kV/III, 8 kV (disconnect) |
| Short circuit current for group motor installation, max | 65kA @ 480V, UL 60947-4-1-manual motor controller |
| Short circuit current for motor disconnect, max | 65kA @ 480V, UL 60947-4-1-manual motor controller |
| Number of poles | 3 |
| With thermal protection | True |
| Phase failure sensitive | True |
| Switch off technique | Thermomagnetic |
| Switching frequency, max | 25 ops/h |
| Trip class | 10 |
| Rated frequency | 45 Hz |
| Phase loss protection | Differential release |
| Fuse or circuit breaker rating with 100-C IEC contactor per NEC, max | 600 A, UL 60947-4-1-manual motor controller |
| Width | 54 mm |
|---|---|
| Depth | 110 mm |
| Height | 111.4 mm |
| Contactor size (Type 2 coordination) with 100-C IEC contactor, min | 100-C37 @ 600V |
| Frame size | Frame size F, 45 A |
| Contactor size, min | 100-C37, UL-508 -Type E self-protected combination motor controller |
| Device construction | Built-in device fixed built-in technique |
| Degree of protection (IP) | IP2X |
|---|---|
| Weight | 782 lb |
| Mechanical life operations | 30000 /h |
| Breaking capacity | High breaking capacity |
| Shock | Transport (60068-2-27): 30 G/11 ms, OFF |
| Protection type | Adjustable thermal/fixed magnetic (13 x In) |
| Factory option | No circuit-breaker auxiliary or trip contacts |
| Vibration | Ops (60068-2-6): 5 G |
| Ambient storage temperature | -40 °C |
|---|---|
| Ambient operating temperature | -25 °C |
| Ambient temperature compensation | -25 °C |
| Site altitude | To 2000 m N.N. (6561 ft) |
| Dependence on temperature | No reduction @ 60 °C (140 °F) |
| Magnetic release current (±20 %) | Fixed setting: 18…22 x Ie maximum (Ie maximum = maximum values of setting ranges) for T version |
| Pollution degree | 3 |
| Climatic resistance | Operating humidity/moisture heat (60068-2-3): 5…95% non-condensing |
| Utilization category | Motor starter: AC-3 (IEC60947-4-1) |
|---|---|
| Overload protection characteristics | IEC 60947-4-1 motor protection |
| Peso | 0.835 kg |
|---|---|
| Dimensiones | 12.49 × 12.29 × 6.19 cm |
| Marcas | Allen-Bradley |
Marca
Rockwell Automation
| Type | Resource | Publication |
|---|---|---|
| General | Product Cutsheet | -- |
| General | Short Circuit Ratings Data Sheet | -- |
| Technical Data | 140m-td002_-en-p | 140M-TD002 |
|
Product Cutsheet
General
-- |
|
Short Circuit Ratings Data Sheet
General
-- |
|
140m-td002_-en-p
Technical Data
140M-TD002 |