Technical Specifications
Electrical
| Number of contacts as normally closed contact | 0 |
|---|---|
| Number of contacts as normally open contact | 2 |
| Rated operational current (Ie) | 3 A @ 24V, 120V, AC-15 per IEC/EN 60947-5-1 for utilization category |
| Rated operation current Ie at AC-15, 230 V | 1.5 A |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Conventional free-air thermal current Ith | 5 A |
| AC thermal rated current | 5 A |
| DC maximum volt-ampere | 28 VA |
| Duty time | 100 % |
| DC thermal rated current | 2.5 A |
| Rated frequency | 50/60 Hz |
| Insulation voltage (Ui) | Rated 250V |
| Switching capacity, min | 17V DC/5 mA |
| Short-circuit protective device | 10 A Type gG |
| Rated operating voltage (Ue) | 250V AC/250V DC |
| AC maximum volt-ampere | Making: 3600VA, Breaking: 360VA |
Construction
| Mounting | Front |
|---|
Environmental
| Pilot duty | B300, R300 |
|---|---|
| Pollution degree | 3 |
| Ambient air temperature | Operation: -25… +60 °C, Storage: -50 … +80 °C |
Mechanical
| Number of operations | 50000 cycles |
|---|---|
| Resistance to shock | 25 G/11 ms per IEC 60068-2-27 |
| Resistance to vibration | 5 G/3 … 150 Hz per IEC 60068-2-6 |
Certification
| Standards compliance | IEC: IEC/EN 60947–1, IEC/EN 60947-5-1, UL/cULus: UL 60947-4-1, CAN/CSA22.2 No. 60947-4-1 |
|---|










There are no reviews yet.