Necesitas Ayuda?+52 55 61 22 77 00
Correo: ventas@omegaautomation.com.mx

140MP-A3E-C20, Motor Protection Circuit Breaker

MXN $6,217.20 - (IVA Incluido) + Envío

4 disponibles

Motor Protection Circuit Breaker

Comprar Ahora
SKU: 140MP-A3E-C20
With integrated under voltage release False
Rated operating voltage 0 A
Type of control element Turn button
Type of electrical connection of main circuit Screw connection
Rated impulse withstand voltage (Uimp) 6 kV
Magnetic trip current 300 A
Short circuit current for group motor, max 18kA @ 480V
Motor current adjustment range 16…20 A
Short circuit current Icu, max 15kA @ 400V
Rated operational current (Ie) 20 A
Ultimate short circuit breaking capacity (Icu) per IEC 6kA @ 500V AC
Rated service short circuit breaking capacity (Ics) per IEC 3kA @ 500V AC
Insulation voltage (Ui) Rated 690V
Hp rating, max 7.5Hp @ 230V, 3-phase
KW rating, max AC-3: 5.5 kW @ 230V, 3-phase
Short circuit current rating Type 1 coordination: 5kA @ 600V AC
Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC 80A @ 690V AC
Branch circuit protection per NEC/CEC, max UL 60947 manual motor controller: 400 A
Trip class 10 A
Fuse or circuit breaker size per NEC, max UL 60947-4-1 manual motor controller: 400 A
Short circuit current, max Type 2 coordination, IEC 60947-4-1: 5kA @ 600V
Fuse or circuit breaker per NEC, max UL 60947-4-1 manual motor controller: 400 A
Short circuit current for group motor installation, max UL 60947 manual motor controller: 5kA @ 600V
Short circuit current for motor disconnect, max UL 60947 manual motor controller: 5kA @ 600V
Number of poles 3
With thermal protection True
Phase failure sensitive True
Max current Ie 32 A
Maximum operating voltage (UL) 600 V
Disconnect function per IEC/EN 60947-2 True
Rated operating voltage (Ue) 690V AC
Rated frequency 50/60 Hz
Number of operations Mechanical: 100.000 cycles, Electrical: 100000 cycles (0.1…16 A), 50000 cycles (20…32 A)
Power loss 5.1 W @ 0.16…1.6 rated operating current, 5.4 @ 2.5…6.3 rated operating current, 7.2 @ 10…12 rated operating current, 8.4 @ 16…25 rated operating current, 9.3 @ 32 rated operating current
Altitude 2000 m
Ambient temperature derating 20A @ 55°C
Pollution degree 3
Storage ambient air temperature -50 °C
Operating ambient air temperature Open compensated: -25…+55 °C, Open: -25…+70 °C, Enclosed: 0…+40 °C
Utilization category Circuit breaker: A per IEC60947-2, Motor starter: AC-3 per IEC60947-4-1
Device construction Built-in device fixed built-in technique
Mounting DIN Rail (EN 60715)
Group mounting side by side Up to 40 °C (104 °F)
Resistance to shock 25 G/11 ms per IEC 60068-2-27
Resistance to vibration 5 G/3 … 150 Hz per IEC 60068-2-6
Degree of protection Housing: IP20, Main terminals: IP10
Peso 0.34 kg
Dimensiones 9.2 × 10 × 4.92 cm
Marcas

Allen-Bradley

Marca

Rockwell Automation

Type Resource Publication
General Product Cutsheet --
General Link to Literature Library for Tech Data 140MP-TD001
Technical Data 140mp-td002_-en-p 140MP-TD002
,
Product Cutsheet General
--
Link to Literature Library for Tech Data General
140MP-TD001
140mp-td002_-en-p Technical Data
140MP-TD002
,

Customers reviews

There are no reviews yet.

Be the first to review “140MP-A3E-C20, Motor Protection Circuit Breaker”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

Search for products

Back to Top
Elegir Moneda
MXN Peso mexicano
Product has been added to your cart