Number of analogue outputs |
1 |
Mains voltage |
400 V |
Integrated breaking resistance |
False |
Internal dynamic brake resistors |
115 ohm |
Brake IGBT |
Brake IGBT installed |
Bus undervoltage output shutoff |
305V DC @ 380/400V |
Bus undervoltage fault level |
300V DC @ 380/400V |
Internal communication module |
No communication module |
AC input undervoltage trip |
233V AC @ 380/400V |
Bus voltage, nom |
540V DC @ 380/400V |
Bus overvoltage trip |
810V DC @ 380/400V |
Circuit breaker current rating, max |
15A @ 400V AC, 3-phase |
Motor circuit protector current rating, max |
7A @ 400V AC, 3-phase |
Output current rating, continuous |
3.5A @ 400V AC, 3-phase |
Output current rating, 1 min |
4.5A @ 400V AC, 3-phase |
Output current rating, 3 sec |
6A @ 400V AC, 3-phase |
Logic control ride-thru |
0.5 s minimum, 2 s typical |
Brake resistor |
Without drive mounted brake resistor |
Input current rating |
4.3A @ 400V AC, 3-phase |
Documentation |
Manual |
Carrier frequency |
Standard control: 2, 3, 4, 5, 6, 7, 8, 9, and 10 kHz, vector control: 2, 4, 8, and 12 kHz, drive rating based on 4 kHz |
Encoder quadrature |
90° ±27° |
AC input overvoltage trip |
475V AC @ 380/400V |
Input power rating |
3 kVA @ 400V AC, 3-phase |
Dual element time delay fuse current rating |
6A @ 400V AC, 3-phase |
Non-time delay fuse current rating |
6…12A @ 400V AC, 3-phase |
Heat sink thermistor |
Monitored by microprocessor overtemp trip |
Drive to motor power ratio, max |
Recommended not greater than 2:1 ratio |
Stop modes |
Multiple progmable stop modes including – RA, Coast, DC-brake, Fast brake, RA-to-hold and S-curve |
Acceleration/deceleration |
Two independently progmable accel and decel times. Each time can be progmed from 0…3600 s in 0.1 s increments |
Frequency accuracy |
Digital input: within ±0.01% of set output frequency |
Number of digital inputs |
6 |
Number of digital outputs |
2 |
Internal watts loss |
21.6 W @ 400V @ 1.5Hp normal duty |
Number of analogue inputs |
2 |
Motor voltage, nom |
460V @ 380…480V drive rating, 480V nominal line voltage |
Human interface model |
No HIM-blank plate |
Supporting protocol for DeviceNet |
True |
Application in industrial area permitted |
True |
External watts loss |
43.6 W @ 400V @ 1.5Hp normal duty |
Total watts loss |
65.2 W @ 400V @ 1.5Hp normal duty |
Line voltage, nom |
480V @ 380…480V drive rating, 460V nominal motor voltage |
Supporting protocol for EtherNet/IP |
True |
Mains frequency |
50 Hz |
Output frequency range |
Standard control: 0…400 Hz, enhanced control: 0…500 Hz |
Internal EMC filtering |
S environment filter per CE EMC directive (89/336/EEC) |
Feedback option |
No ftdback |
Drive full power range |
460…528V @ 380…480V drive rating, 460V nominal motor voltage |
Drive operating range |
342…528V @ 380…480V drive rating, 460V nominal motor voltage |
Torque regulation |
Without ftdback +/-10%, with ftdback +/-5% |
Enclosure type |
Panel mount-IP20/NEMA Type 1 |
Output current rating |
3.5 A, 1.5 kW normal duty, 1.1 kW heavy duty, frame A |
Cooling fan operation |
Frames B, D, and E: fan operates when power is applied and in run condition |
Control options |
Enhanced control with 24V I/O |
Drive overcurrent trip |
Software current limit: 20…160% of rated current |
Efficiency |
97.5% at rated A, nominal line volts |
Encoder supply |
5V/12V configurable ±5% |
Speed control-speed regulation |
Without ftdback (Vector Control mode): 0.1% of base speed across 120:1 speed range, 120:1 operating range, 30 rad/sec bandwidth |
Current limit capability |
Proactive current limit progmable from 20…160% of rated output current, Independently progmable proportional and integral gain |
Selectable motor control |
Sensorless vector with full tuning. Standards V/Hz with full custom capability and vector control |
Frequency control-speed regulation |
With slip compensation (Volts per Hz mode): 0.5% of base speed across 40:1 speed range, 40:1 operating range, 10 rad/sec bandwidth |
Input phases |
Three-phase input provides full rating for all drives. single-phase ops provides 50% of rated current |
Control method |
Sine coded PWM with progmable carrier frequency. Ratings apply to all drives |
Number of HW-interfaces RS-232 |
2 |
Number of HW-interfaces RS-485 |
2 |
Number of HW-interfaces USB |
2 |
Number of phases output |
3 |
Number of phases input |
3 |
Relative symmetric net voltage tolerance |
10 % |
With control element |
True |
Supporting protocol for TCP/IP |
True |
Supporting protocol for PROFIBUS |
True |
Supporting protocol for CAN |
True |
Supporting protocol for Modbus |
True |
Application in domestic- and commercial area permitted |
True |
Motor overload protection |
Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C file E59272 |
Input frequency tolerance |
47 Hz |
Encoder duty cycle |
50% ±10% |
Voltage tolerance |
-10 % |
Displacement power factor (all drives) |
0.98 across speed range |
Short circuit rating, max |
200000 A symmetrical |
Output voltage range |
0 to rated motor voltage |
Encoder type |
Incremental, dual channel |
Power ride-thru |
15 ms at full load |
Short circuit trip |
Phase-to-phase on drive output |
Ground fault trip |
Phase-to-ground on drive output |
Drive to motor power ratio, min |
Recommended not less than 1:2 ratio |
Control logic noise immunity |
Showering arc transients upto 1500V peak |
Line transients |
Up to 6000 volts peak per IEEE C62.41-1991 |
Short circuit current rating, max |
Maximum short circuit current rating to match specified fuse/circuit breaker capability |
Intermittent overload |
110% overload capability for up to 1 min, 150% overload capability for up to 3 s |
There are no reviews yet.