Number of analogue outputs |
2 |
Mains voltage |
480 V |
Integrated breaking resistance |
False |
Max. output voltage |
932 V |
Internal dynamic brake resistors |
68 ohm |
DC bus overvoltage trip |
810V DC @ 480V |
DC nominal bus voltage |
648V DC @ 480V |
Brake IGBT |
Brake IGBT installed |
Internal communication module |
ControlNet coaxial |
Fuse current rating |
60A @ 650V DC |
Input voltage rating |
480V AC, 3-phase, 60 Hz |
Displacement power factor |
0.98 across speed range |
Output current, continuous |
34A @ 650V DC |
Output current, 1 min |
40.5A @ 650V DC |
Output current, 3 sec |
54A @ 650V DC |
Circuit breaker current rating, max |
125A @ 480V AC, 3-phase |
Motor circuit protector current rating, max |
50A @ 480V AC, 3-phase |
Logic control ride-thru |
0.25 s, drive not running |
Brake resistor |
No internal brake resistor |
Input current rating |
36.4A @ 650V DC |
Rated power rating |
25Hp @ 650V DC, normal duty |
Documentation |
English documentation |
Carrier frequency |
Drive rating: 4 kHz, settings: 2, 4, 6, 8, 10 kHz (6 kHz is for V/Hz ops only) |
AC input overvoltage trip |
600V AC @ 480V (six pulse, 3-phase) |
Input power rating |
25.9 kVA @ 480V AC, 3-phase |
Electronic motor overload protection |
Class 10 motor overload protection according to NEC article 430 and motor over-temperature protection according to NEC article 430.126 (A)(2). UL 508C file E59272 |
Dual element time delay fuse current rating |
40…70A @ 480V AC, 3-phase |
Non-time delay fuse current rating |
40…125A @ 480V AC, 3-phase |
Heat sink thermistor |
Monitored by microprocessor overtemperature trip |
Drive to motor power ratio, max |
The drive to motor rating cannot exceed a 2:1 ratio |
Stop modes |
Multiple progmable stop modes including – RA, Coast, and Current Limit |
Acceleration/deceleration |
Independently progmable accel and decel times adjustable from 0 to 6553.5 in 0.1 s increments |
Number of digital inputs |
6 |
Number of digital outputs |
2 |
Number of analogue inputs |
3 |
Motor voltage, nom |
460V @ 380…400V drive rating, 480V nominal line voltage |
Human interface model |
No HIM (no blank plastic inserted) |
Additional configuration |
Phase II control |
Max. output frequency |
400 Hz |
Line voltage, nom |
480V @ 380…400V drive rating, 460V nominal motor voltage |
Mains frequency |
60 Hz |
Internal EMC filtering |
With EMC filter & common mode choke |
Watt loss |
519 W @ 480V AC @ 25Hp normal duty, 20 Hp heavy duty |
Feedback option |
Future use |
Drive full power range |
460…528V @ 380…400V drive rating, 460V nominal motor voltage |
Drive operating range |
325…528V @ 380…400V drive rating, 460V nominal motor voltage |
Torque regulation |
Torque regulation – without ftdback: ±5%, 600 rad/sec bandwidth |
Enclosure type |
IP20/NEMA/UL Type 1 |
Output current rating |
34 A, 25 Hp normal duty, 20 Hp heavy duty, frame 2 |
Control options |
Phase II control, expanded cassette |
Drive overcurrent trip |
Software current limit: 105% of motor rated to 200% of drive rated current |
Efficiency |
97.5% at rated A, nominal line volts |
Speed control |
Speed regulation – without ftdback: 0.1% of base speed across 120:1 speed range, 120:1 operating range, 50 rad/sec bandwidth |
Current limit capability |
Independent motoring and regenerative power limits progmable to 800% of rated output current |
Selectable motor control |
Field oriented control with and without a ftdback device and permanent magnet motor control |
Input phases |
Six-pulse, 3-phase input provides full rating for all drives, single-phase ops provides 50% of rated current |
Control method |
Induction motor and brushless motor: sine coded PWM with progmable carrier frequency, indirect self organized, field-oriented control, current-regulated, ratings apply to all drives, refer to the PowerFlex 700S Phase ll control reference manual, public |
Number of phases output |
3 |
Number of phases input |
3 |
Relative symmetric net voltage tolerance |
10 % |
Input frequency, max |
400 Hz |
Output frequency range |
0 Hz |
DC bus undervoltage trip |
Adjustable |
Output voltage range |
0 to rated motor voltage |
Power ride-thru |
15 ms at full load |
S-curve time |
Adjustable 0.5…4.0 s |
Short circuit trip |
Phase-to-phase on drive output |
Ground fault trip |
Phase-to-ground on drive output |
Control logic noise immunity |
Showering arc transients upto 1500V peak |
Line transients |
Up to 6000 volts peak per IEEE C62.41-1991 |
Intermittent overload |
110% overload capability for up to 1 min, 150% overload capability for up to 3 s |
Short circuit current, max |
Using recommended fuse or circuit breaker type: maximum short circuit current rating to match specified fuse/circuit breaker capability ≤200000 A |
Encoder voltage supply |
5V DC or 12V DC 320 mA/channel, 5V DC minimum high state voltage state of 0.4V DC @ 12V DC minimum high state voltage of 7.0V DC, maximum low state voltage of 0.4V DC |