Necesitas Ayuda?+52 55 61 22 77 00
Correo: ventas@omegaautomation.com.mx

ABLS1A24031, Regulated Power Supply, 100 to 240V AC, 24V, 3.1A, single phase, Optimized

MXN $2,167.00 - (IVA Incluido) + Envío

6 disponibles

This ABLS regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 240V AC and 140 V to 340 V DC, a rated output current of 3,13A at 24V DC and a rated power output of 75W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. It installs on omega rail or fixing by screw. Its width is 27mm, its height is 123,6mm, its depth is 102mm. It ensures a protection against overloads and short-circuits with automatic restart after the source of overload/short-circuit has been corrected. It weighs 0.220kg. It is a power supply for industrial use, rail mounting. It conforms to EN62368-1, ENIEC61010-1/2-201, ENIEC61204-3, EN61000-6-1/2/3/4, EN61000-3-2-3, UL62368-1, UL61010-2-201/-1-201, CSAC22.2No62368-1/No61010-2-201/No61010-1 standards, and certified by CE, CUL listed/recognized, RCM, CBscheme. The Acti9 iC60 range of Miniature Circuit Breakers is recommanded for its protection. The type of protection is 10A, C curve or 13A, B-curve. It has in the front face a LED indicating presence of DC output voltage, and a QR code for access to the latest technical documentation. Thanks to its book housing, it can be installed either in enclosures or industrial panels by clipping on omega (DIN) rail. It brings energy to your automated systems. Designed for simple machines and applications, modular power supplies are primarily appreciated for their extreme compactness.

Comprar Ahora
SKU: ABLS1A24031
Main
Range of Product Modicon Power Supply
Product or Component Type Power supply
Power supply type Regulated switch mode
Variant option Optimized
Enclosure Material Plastic
Nominal input voltage 100…240 V AC single phase
100…240 V AC phase to phase
140…340 V DC
Kw Rating 75 W
Output voltage 24 V DC
Power supply output current 3.13 A
Complementary
Efficiency at full load 85…264 V AC without temperature derating
120…375 V DC without temperature derating
Nominal network frequency 50…60 Hz
Network system compatibility TN
TT
IT
Maximum leakage current 1 mA 240 V AC
Input protection type Integrated fuse (not interchangeable) 5 A
External protection (recommended) 20 A Curve C
External protection (recommended) 13 A Curve B
External protection (recommended) 10 A Curve C
Inrush current 40.0 A 115 V
80.0 A 230 V
Power factor 0.55 at 115 V AC
0.45 at 230 V AC
Efficiency 88 % 230 V AC
Output voltage adjustment 21.6…26.4 V
Power dissipation in W 15 W
Current consumption < 1.8 A 115 V AC
< 1 A 230 V AC
< 0.8 A 140 V DC
Turn-on time < 1.2 s
Holding time > 20 ms 115 V AC
> 40 ms 230 V AC
Startup with capacitive loads 5000 µF
Residual ripple < 120 mV
Meantime between failure [MTBF] 700000 h at 77 °F (25 °C), full load conforming to SR 332
Output protection type Against overload and short-circuits, protection technology: automatic reset
Against over temperature, protection technology: manual reset
Against overvoltage, protection technology: manual reset
Connections – terminals Screw connection 0.5…2.5 mm², AWG 20…AWG 14) output
Screw connection 0.75…2.5 mm², AWG 18…AWG 14) input
Line and load regulation < 0.5 % network 0 to 100 % load at 77 °F (25 °C)
< 1 % network full voltage range in line at 77 °F (25 °C)
Status LED 1 LED (Green) output voltage
Depth 4.02 in (102 mm)
Height 4.9 in (123.6 mm)
Width 1.06 in (27 mm)
Net Weight 0.49 lb(US) (0.22 kg)
Output coupling Parallel
Serial
Mounting support Top hat type TH35-15 rail IEC 60715
Top hat type TH35-7.5 rail IEC 60715
Double-profile DIN rail
Supply SELV IEC 60950-1
SELV IEC 60204-1
SELV IEC 60364-4-41
Dielectric strength 3000 V AC with input to output
Service life 10 year(s)
Overvoltage category II
Environment
Standards IEC 62368-1
EN/IEC 61010-1
EN 61010-2-201
EN/IEC 61204-3
IEC 61000-6-1
IEC 61000-6-2
IEC 61000-6-3
IEC 61000-6-4
IEC 61000-3-2
EN 61000-3-3
UL 62368-1
UL 61010-1
UL 61010-2-201
CSA C22.2 No 62368-1
CSA C22.2 No 61010-1
CSA C22.2 No 61010-2-201
EN/IEC 62368-1
Product certifications CE
CUL Listed
CUL Recognized
RCM
CB Scheme
EAC
KC
NEC class 2
Operating altitude < 5000 m
Shock resistance 150 m/s² 11 ms
IP degree of protection IP20
Ambient air temperature for operation -4…14 °F (-20…-10 °C) with current derating of 1 % per °C mounting position A < 6561.68 ft (2000 m)
14…104 °F (-10…40 °C) without derating mounting position A 115 V AC < 6561.68 ft (2000 m)
14…122 °F (-10…50 °C) without derating mounting position A 230 V AC < 6561.68 ft (2000 m)
104…158 °F (40…70 °C) with current derating of 1.67 % per °C mounting position A 115 V AC < 6561.68 ft (2000 m)
122…158 °F (50…70 °C) with current derating of 2.5 % per °C mounting position A 230 V AC < 6561.68 ft (2000 m)
Electrical shock protection class Class I
Pollution degree 2
Vibration resistance 3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6
10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6
Electromagnetic immunity Immunity to electrostatic discharge – test level: 8 kV (contact discharge) conforming to IEC 61000-4-2
Immunity to electrostatic discharge – test level: 15 kV (air discharge) conforming to IEC 61000-4-2
Immunity to conducted RF disturbances – test level: 15 V/m (80 MHz…2 GHz) conforming to IEC 61000-4-3
Immunity to conducted RF disturbances – test level: 5 V/m (2…2.7 GHz) conforming to IEC 61000-4-3
Immunity to conducted RF disturbances – test level: 5 V/m (2.7…6 GHz) conforming to IEC 61000-4-3
Immunity to fast transients – test level: 4 kV (on input-output) conforming to IEC 61000-4-4
Surge immunity test – test level: 4 kV (between power supply and earth) conforming to IEC 61000-4-5
Surge immunity test – test level: 3 kV (between phases) conforming to IEC 61000-4-5
Immunity to conducted RF disturbances – test level: 15 V (0.15…80 MHz) conforming to IEC 61000-4-6
Immunity to magnetic fields – test level: 30 A/m (50…60 Hz) conforming to IEC 61000-4-8
Immunity to voltage dips conforming to IEC 61000-4-11
Disturbing field emission conforming to EN 55016-2-3
Limits for harmonic current emissions conforming to IEC 61000-3-2
conforming to EN 55016-1-2
conforming to EN 55016-2-1
Electromagnetic emission Conducted emissions IEC 61000-6-3
Radiated emissions IEC 61000-6-4
Ordering and shipping details
Category US1CP1222525
Discount Schedule CP12
GTIN 3606481500205
Returnability Yes
Country of origin IN
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 1.46 in (3.700 cm)
Package 1 Width 5.51 in (14.000 cm)
Package 1 Length 6.30 in (16.000 cm)
Package 1 Weight 11.393 oz (323.000 g)
Unit Type of Package 2 S03
Number of Units in Package 2 22
Package 2 Height 11.81 in (30.000 cm)
Package 2 Width 11.81 in (30.000 cm)
Package 2 Length 15.75 in (40.000 cm)
Package 2 Weight 16.830 lb(US) (7.634 kg)
Unit Type of Package 3 P06
Number of Units in Package 3 176
Package 3 Height 29.53 in (75.000 cm)
Package 3 Width 23.62 in (60.000 cm)
Package 3 Length 31.50 in (80.000 cm)
Package 3 Weight 147.710 lb(US) (67.000 kg)
Peso 0.323 kg
Dimensiones 16 × 14 × 3.7 cm

Marca

Schneider Electric

Documentos
 
 

Customers reviews

There are no reviews yet.

Be the first to review “ABLS1A24031, Regulated Power Supply, 100 to 240V AC, 24V, 3.1A, single phase, Optimized”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

Search for products

Back to Top
Elegir Moneda
MXN Peso mexicano
Product has been added to your cart