Technical Specifications
Electrical
Rated apparent power | 250 VA |
---|---|
Secondary voltage | 120V-60 Hz |
Fuse block option | 2 primary-1 secondary |
Secondary fuse size | 3.2 A @ 120V (per NEC) |
Primary voltage | 208V-60 Hz |
Factory installed options | No cover/no secondary fuse |
Inrush VA | 781VA @ 95% of rated secondary voltage, 40% power factor |
Primary fuse size | 6 A @ 208V (when primary and secondary protection is used per NEC) |
Short-circuit-proof | No |
Construction
Bulk package | Single pack |
---|---|
Depth | Without fusing: 4-7/8 inch (123.95 mm) |
Width | Without fusing: 4-1/2 inch (114.30 mm) |
Height | Without fusing: 3-29/32 inch (98.30 mm) |
Shipping weight, approx | Without top mounted fuse block: 10-2/5 lb (4.72 Kg) |
Modular version | No |
Ring core | No |
Built as energy saving transformer | No |
Built as safety transformer | No |
Built as isolating transformer | No |
Conductor material | Copper |
Environmental
Type of insulation material according to IEC 85 | B |
---|
Mechanical
Suitable for mounting on PCB | No |
---|