Motor controller, TeSys T, Motor Management, DeviceNet, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 100 to 240VAC
LTMR100DFM
Range | TeSys |
---|---|
Product name | TeSys T |
Device short name | LTMR |
Product or Component Type | Motor controller |
Device Application | Equipment monitoring and control |
Measurement current | 5…100 A |
[Us] rated supply voltage | 100…240 V AC 50/60 Hz |
Current Consumption | 8…62.8 mA |
Supply voltage limits | 93.5…264 V AC |
Communication Port Protocol | DeviceNet |
Bus type | DeviceNet ISO 1198 1…64 125…500 kbit/s, terminal block 4 twisted shielded pairs cable |
[Ui] rated insulation voltage | 690 V EN/IEC 60947-1 690 V CSA C22.2 No 14 690 V UL 508 |
---|---|
[Uimp] rated impulse withstand voltage | 4 kV supply, inputs and outputs EN/IEC 60947-4-1 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 0.8 kV communication circuit EN/IEC 60947-4-1 |
Short-circuit withstand | 100 kA conforming to EN/IEC 60947-4-1 |
Associated fuse rating | 4 A gG output 0.5 A gG control circuit |
Protection Type | Phase failure Overload (long time) Load fluctuation Thermal overload protection Power factor variation Overload Locked rotor Thermal protection Earth-leakage protection Phase unbalance Reverse polarity protection |
Network and machine diagnosis type | Motor control command recording Trip history information Running hours counter/operating time Phase fault and earth fault trip counters Remaining operating time before overload tripping Fault recording Trip context information Event recording Starting current and time Waiting time after overload tripping |
Logic input number | 6 |
Input current | 3.1 mA 100 V 7.5 mA 240 V |
Current state 0 guaranteed | Logic input 0…40 V <= 15 mA 25 ms |
Current state 1 guaranteed | Logic input 79…264 V >= 2 mA 25 ms |
maximum output switching frequency | 2 Hz |
Load current | 5 A 250 V AC logic output 5 A 30 V DC logic output |
Permissible power | 480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output) |
Maximum operating rate | 1800 cyc/h |
Contacts type and composition | 1 NO + 1 NC fault signal 3 NO |
Metering type | Imbalance current Temperature Average current Iavg Earth-fault current Phase current I1, I2, I3 RMS |
Measurement accuracy | 5…15 % earth fault current internal measurement 1 % voltage 100…830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 Temperature 5 % active and reactive power 0,02 current |
Overvoltage category | III |
Connection pitch | 0.20 in (5.08 mm) |
Connections – terminals | Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24…AWG 14)flexible with cable end Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24…AWG 14)flexible without cable end Control circuit connector 1 0.0004…0.004 in² (0.25…2.5 mm²) AWG 24…AWG 14)flexible without cable end Control circuit connector 1 0.0003…0.004 in² (0.2…2.5 mm²) AWG 24…AWG 14)solid without cable end Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24…AWG 14)flexible with cable end Control circuit connector 2 0.0003…0.002 in² (0.2…1.5 mm²) AWG 24…AWG 14)flexible without cable end Control circuit connector 2 0.0008…0.002 in² (0.5…1.5 mm²) AWG 24…AWG 14)flexible without cable end Control circuit connector 2 0.0003…0.002 in² (0.2…1 mm²) AWG 24…AWG 14)solid without cable end |
Tightening torque | Control circuit 4.4…5.3 lbf.in (0.5…0.6 N.m) flat 0.1 in (3 mm) |
Pollution degree | 3 |
Electromagnetic compatibility | Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 |
Width | 3.6 in (91 mm) |
Height | 2.4 in (61 mm) |
Depth | 4.8 in (122.5 mm) |
Net Weight | 1.17 lb(US) (0.53 kg) |
Web services | Web server |
Compatibility code | LTMR |
Standards | EN 60947-4-1 UL 508 IEC 60947-4-1 CSA C22.2 No 14 IACS E10 |
---|---|
Product Certifications | CSA DNV LROS (Lloyds register of shipping) RINA EAC GL UL ATEX BV CCC RMRoS KERI ABS NOM C-tick |
Protective treatment | 12 x 24 hour cycles EN/IEC 60068-2-30 48 h EN/IEC 60070-2-11 TH EN/IEC 60068 |
Fire resistance | 1202.0000000000 °F (650 °C) EN/IEC 60695-2-12 1760.0000000000 °F (960 °C) UL 94 |
Ambient air temperature for operation | -4.0000000000…140.0000000000 °F (-20…60 °C) |
Ambient Air Temperature for Storage | -40.0000000000…176.0000000000 °F (-40…80 °C) |
Operating altitude | <= 6561.68 ft (2000 m) without derating |
Mechanical robustness | Vibrations mounted on symmetrical rail1 Gn, 5…300 Hz EN/IEC 60068-2-6 Vibrations plate mounted4 Gn, 5…300 Hz EN/IEC 60068-2-6 Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27 |
IP Degree of Protection | IP20 |
Category | US10I1222338 |
---|---|
Discount Schedule | 0I12 |
GTIN | 3389119404792 |
Returnability | No |
Country of origin | SG |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 2.8 in (7.0 cm) |
Package 1 Width | 3.9 in (10.0 cm) |
Package 1 Length | 5.3 in (13.5 cm) |
Package 1 Weight | 18.5 oz (524.0 g) |
Unit Type of Package 2 | S02 |
Number of Units in Package 2 | 10 |
Package 2 Height | 5.9 in (15.0 cm) |
Package 2 Width | 11.8 in (30.0 cm) |
Package 2 Length | 15.7 in (40.0 cm) |
Package 2 Weight | 12.403 lb(US) (5.626 kg) |
Warranty | 18 months |
---|
There are no reviews yet.