Necesitas Ayuda?+52 55 61 22 77 00
Correo: ventas@omegaautomation.com.mx

1408-TS3A-ENT, PowerMonitor 1000, Volt & Current, ENet

MXN $53,015.60 - (IVA Incluido) + Envío

Sin existencias

PowerMonitor 1000, Volt & Current, ENet

SKU: 1408-TS3A-ENT
Vibration 2.0 G @ 10…500 Hz
Shock Operating : 30 G peak each axis
Dielectric withstand UL61010, EN61010 pollution degree 2
Storage temperature -40 to 85 °C
Operating temperature -10 to 60 °C
Humidity 5…95% noncondensing
Terminal blocks 0.34…2.5 mm² (22 AWG), 75 °C (167 °F) min copper wire only recommended torque 0.8 N.m (7 in-lb)
Control power 85…264V AC, 47…63 Hz 125…250V DC 4VA maximum
Current sense inputs: I1, I2, I3 Starting current : 5 mA
Voltage sense inputs: V1, V2, V3, max Input current : 2 mA
Voltage sense inputs: V1, V2, V3, min Input impedance : 5 MΩ
Status inputs Contact closure (internal 24V DC)(except BC3)
Configurable via webpage True
Display (integrated LCD) True
CIP energy object True
Control power 85…264V AC, 47…63 Hz 125…250V DC 4VA maximum
Current sense inputs: I1, I2, I3 Starting current : 5 mA
Voltage sense inputs: V1, V2, V3, max Input current : 2 mA
Voltage sense inputs: V1, V2, V3, min Input impedance : 5 MΩ
Control power and ground wiring terminals 120…240V AC, 50…60 Hz
Accuracy Voltage sense inputs: ±0.5% @ 25°C, 50/60 Hz, unity Power Factor, line-neutral rms : 347V nom / 15…399V
Voltage sensing wiring terminals Direct connect up to 600V AC three-phase line-to-line, Maximum nominal line-to-ground voltage 347V, Use potential transformers (PTs) for higher voltages.
Ethernet network port – standard RJ45 jack with status indicators Ethernet network port hardware is included on all models. the port functions only on units ordered with or upgraded to the Ethernet network. the following protocols and functions are supported. Ethernet/IP Modbus TCP HTML webpage for configuration and data access lnk indicator solid green: IP link established OFF : no link established act indicator flashing yellow: data present on Ethernet port OFF : no data activity present
DIN rail clips Top and bottom clips for mounting unit on DIN rail
Configuration lock wiring terminals Wire together to help prevent configuration changes
LCD Unit configuration data display – not present on BC3 model
LCD interface buttons Unit configuration data display navigation not present on BC3 model
KYZ-output wiring terminals DPDT solid-state relay for signaling use – not present on BC3 model
Mac ID label Aa:bb:cc:dd:ee:ff, used when assigning an IP address using DHCP, X, X, X
Current sensing wiring terminals Nominal input current 5 A, Use current transformers (CTs) to connect to power system
Serial port status indicators Tx indicator flashes yellow when data is being transmitted Rx indicator flashes yellow when data is being received
Status-input wiring terminals Restore factory defaults wiring terminals (BC3) Two internally-powered inputs (TS3, EM3), S2 can be used for demand period synchronization (TS3, EM3), FD1 and FD2 can be used to restore factory default configuration (BC3).
Serial port – three-pin RS-485 connector All models include RS-485 serial communication that supports the following protocols and functions. DF1 half-duplex slave, DF1 full-duplex, Modbus RTU slave, Configuration by using terminal emulation software, DH-485.
Module and network status indicators Module indicator GREEN: normal ops Alternating RED/GREEN: performing self-test RED (solid or blinking): initial power-up or failed self-test. network indicator GREEN: Ethernet connection established Blinking GREEN: Ethernet port looking for a connection RED: duplicate IP address detected.
Frequency Hz: Yes
Reactive power (kVAR) True
Current True
Real power (kW) True
Apparent power (kVA) True
True power factor True
Real power consumption (kWh) True
Reactive power consumption (kVARh) True
Apparent power consumption (kVAh) True
Voltage unbalance True
Current unbalance True
Voltage True
Description PowerMonitor 1000 energy, demand, and PowerMonitor with serial network communication
Ampere meter True
Blind power meter True
Frequency meter True
Pulse counter True
Voltmeter True
Effective power measurement device True
Time of use log True
Energy log True
Minimum/maximum log True
Unit status log True
Alarm log True
Digital output True
Digital accuracy Class1
Consumption + volt/current w/ Ethernet True
Peso 0.519 kg
Dimensiones 20.44 × 11.43 × 14.85 cm
Marcas

Allen-Bradley

Marca

Rockwell Automation

Type Resource Publication
General Product Profile --
General Product Cutsheet --
,
Product Profile General
--
Product Cutsheet General
--
,

Customers reviews

There are no reviews yet.

Be the first to review “1408-TS3A-ENT, PowerMonitor 1000, Volt & Current, ENet”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

Search for products

Back to Top
Elegir Moneda
MXN Peso mexicano
Product has been added to your cart