discrete I/O module Modicon Quantum – 16 I – 115 V AC – 8 O solid state
140DAM59000
| Range of Product | Modicon Quantum automation platform |
|---|---|
| Product or Component Type | Mixed discrete I/O module |
| Discrete I/O number | 24 |
| Discrete input number | 16 2 groups of 8 |
|---|---|
| Addressing requirement | 1 input word 0.5 output word |
| network frequency limits | 47…63 Hz |
| Discrete input voltage | 115 V AC |
| Input voltage limits | 156 V during 10 s 200 V during one cycle 132 V typical |
| Voltage state 0 guaranteed | 0…20 V |
| Voltage state 1 guaranteed | 79…132 V 60 Hz 85…132 V 50 Hz |
| Current state 0 guaranteed | <= 0.5 mA |
| Current state 1 guaranteed | <= 11 mA 50 Hz <= 13.2 mA 60 Hz |
| Input impedance | 14400 Ohm capacitive |
| Response time | 4.9…0.75 ms at state 0 to state 1 7.3…12.3 ms at state 1 to state 0 |
| Discrete output number | 8 2 groups of 4 |
| Discrete output type | Solid state |
| Discrete output voltage | 115 V |
| Output voltage limits | 156 V AC during 10 s 200 V AC during 1 cycle 85…132 V typical AC typical |
| Minimum load | 5 mA |
| Maximum load current | <= 4 A per point <= 8 A per group <= 8 A per module |
| Maximum voltage drop | <1.5 V |
| Absolute maximum output | 20 A 2 cycles per point 26 A 3 cycles per group 30 A 1 cycle per point 30 A 2 cycles per group 45 A 1 cycle per group 10 A 3 cycles per point |
| DV/dt | 400 V/µs |
| Maximum leakage current | 2.1 mA 115 V AC input circuit 2 mA output circuit |
| Response time on output | <= 0.5 ms at state 0 to state 1 <= 0.5 ms at state 1 to state 0 |
| Protection Type | On output by RC filter Internal output protection by 5 A fuse per group |
| Isolation between group | 1000 Vrms for 1 minute |
| Isolation between channels and bus | 1780 Vrms for 1 minute |
| Fault indication | Loss of field power on output Blown fuse on output |
| Power dissipation | 5.5 W + (1.1 x total module load current) |
| External power requirement | 85…132 V AC for output circuit |
| Local signalling | for bus communication is present (Active) 1 LED (green) for no voltage in output and input (F) 1 LED (red) for output is turned on 2 LEDs (green) for fault detected on the input point 2 LEDs (red) for fault detected on the output point 2 LEDs (red) |
| marking | CE |
| Bus current requirement | 250 mA |
| Net Weight | 0.99 lb(US) (0.45 kg) |
| Resistance to electrostatic discharge | 4 kV contact IEC 801-2 8 kV on air IEC 801-2 |
|---|---|
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80…1000 MHz IEC 801-3 |
| Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Relative Humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
| Standards | FM Class 1 Division 2 UL 508 CSA C22.2 No 142 |
| Product Certifications | cUL |
| Category | US1PC2118155 |
|---|---|
| Discount Schedule | PC21 |
| GTIN | 3595861126954 |
| Returnability | No |
| Country of origin | FR |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.4 in (16.3 cm) |
| Package 1 Width | 1.8 in (4.5 cm) |
| Package 1 Length | 12.3 in (31.2 cm) |
| Package 1 Weight | 19.8 oz (560.0 g) |
| Warranty | 18 months |
|---|


There are no reviews yet.