With integrated auxiliary switch |
False |
With integrated under voltage release |
False |
Rated short-circuit breaking capacity lcu at 400 V, AC |
100 kA |
Rated operation power at AC-3, 400 V |
0.75 kw |
Rated operation power at AC-3, 230 V |
0.37 kw |
Rated operating voltage |
230 A |
Type of control element |
Turn button |
Overload release current setting |
1.6 A |
Type of electrical connection of main circuit |
Screw connection |
Magnetic release current per IEC |
33 A |
Rated operational current (Ie) per IEC |
2.5 A |
Magnetic trip current |
33 A |
Short circuit current (Type 2 coordination), max-inv |
50kA @ 480V |
Current range |
1.6…2.5 A |
Ultimate short circuit breaking capacity (Icu) per IEC |
6kA @ 690V |
Rated service short circuit breaking capacity (Ics) per IEC |
6kA @ 690V |
Hp rating, max |
2Hp @ 575V, 3-phase |
Rated operating voltage, max |
690V per IEC, SEV, VDE0660 |
Electrical life cycle |
(Ie max.) 100000 ops |
Short circuit current for combination motor controller with 100-K contactor, max-inv |
65 kA @ 480Y/277V, UL 508-Type F |
Short circuit current for combination motor controller with 100-C contactor, max-inv |
65 kA @ 480Y/277V, UL 508-Type F |
Short circuit current for self-protected combination motor controller with 100-C contactor, max-inv |
65 kA @ 480Y/277V, UL 508-Type E |
Switching of standard motors per IEC |
1.8 kW @ 690V, 3-phase |
KW rating, max |
1.8 kW @ 690V (AC-3), 3-phase |
Back up fuse (gG, gL) current rating (if Icc ≥ Icu ) per IEC |
No back-up fuse required @ 500V |
Short circuit current for group motor installation with 100-K contactor, max-inv |
65kA @ 480V, UL 508-manual motor controller |
Short circuit current for motor disconnect with 100-K contactor, max-inv |
65kA @ 480V, UL 508-manual motor controller |
Short circuit current for group motor installation with 100-C contactor, max-inv |
65kA @ 480V, UL 508-manual motor controller |
Short circuit current for motor disconnect with 100-C contactor, max-inv |
65kA @ 480V, UL 508-manual motor controller |
Rated thermal current |
0.1…32A @ 60°C ambient temperature (Ith)-inv |
Short circuit current for tap conductor protection, max |
65 kA @ 480Y/277V per UL 508-manual motor controller |
Short circuit current for combination motor controller, max |
65kA @ 480V/277V per UL 508-self-protected (Type E) |
Fuse or circuit breaker per NEC, max |
450 A, UL 508-manual motor controller |
Fuse or circuit breaker rating per NEC, max |
450 A, UL 508-manual motor controller with 100-C contactor |
Short circuit current for group motor installation, max |
65kA @ 480V, UL 508-manual motor controller |
Short circuit current for motor disconnect, max |
65kA @ 480V, UL 508-manual motor controller |
Magnetic release current |
Fixed setting 13…14 x Ie max. Ie max. = maximum values of setting ranges, (±20 %) |
Number of poles |
3 |
With thermal protection |
True |
Phase failure sensitive |
True |
Switch off technique |
Thermomagnetic |
Switching frequency, max |
25 ops/h |
Trip class |
10 |
Rated frequency |
50/60 Hz |
Rated supply current |
0.1 A |
Total power loss (Pv) for circuit breaker at rated load operating temperature-inv |
6 W |
Phase loss protection |
Differential release |
Fuse or circuit breaker rating with 100-K contactor per NEC, max |
450 A, UL 508-manual motor controller |
Main circuits/overvoltage category |
6kV/III @ rated impulse withstand voltage (Uimp) |
Auxiliary circuits/overvoltage category-inv |
6kV/III @ rated impulse withstand voltage (Uimp) |
There are no reviews yet.