Contactor, high power, TeSys Giga, standard version, 3 pole/NO, AC-3 <=440V 330A, 100-250VAC/DC coil
LC1G330KUEN
Range | TeSys |
---|---|
Range of Product | TeSys Giga |
Product or Component Type | Contactor |
Device short name | LC1G |
contactor application | Power switching Motor control |
Utilisation category | AC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8a AC-8b DC-1 DC-3 DC-5 |
poles description | 3P |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz <= 460 V DC |
[Ie] rated operational current | 440 A (at <104 °F (40 °C)) at <= 1000 V AC-1 330 A (at <140 °F (60 °C)) at <= 440 V AC-3 |
[Uc] control circuit voltage | 100…250 V AC 50/60 Hz 100…250 V DC |
Control circuit voltage limits | Operational: 0.8 Uc Min…1.1 Uc Max (at <140 °F (60 °C)) Drop-out: 0.1 Uc Max…0.45 Uc Min (at <140 °F (60 °C)) |
[Uimp] rated impulse withstand voltage | 8 kV |
---|---|
Overvoltage category | III |
[Ith] conventional free air thermal current | 440 A (at 104 °F (40 °C)) |
Rated breaking capacity | 2940 A at 440 V |
[Icw] rated short-time withstand current | 2.65 kA – 10 s 1.8 kA – 30 s 1.3 kA – 1 min 0.9 kA – 3 min 0.75 kA – 10 min |
Associated fuse rating | 400 A aM at <= 440 V for motor 250 A aM at <= 690 V for motor 500 A gG at <= 690 V |
Average impedance | 0.000144 Ohm |
[Ui] rated insulation voltage | 1000 V |
Power dissipation per pole | 30 W AC-1 – Ith 440 A 16 W AC-3 – Ith 330 A |
Compatibility code | LC1G |
Pole contact composition | 3 NO |
Auxiliary contact composition | 1 NO + 1 NC |
Motor power kW | 90 kW at 230 V AC 50/60 Hz (AC-3e) 160 kW at 400 V AC 50/60 Hz (AC-3e) 160 kW at 415 V AC 50/60 Hz (AC-3e) 185 kW at 440 V AC 50/60 Hz (AC-3e) 200 kW at 500 V AC 50/60 Hz (AC-3e) 220 kW at 690 V AC 50/60 Hz (AC-3e) 185 kW at 1000 V AC 50/60 Hz (AC-3e) 90 kW at 230 V AC 50/60 Hz (AC-3) 160 kW at 400 V AC 50/60 Hz (AC-3) 160 kW at 415 V AC 50/60 Hz (AC-3) 200 kW at 440 V AC 50/60 Hz (AC-3) 200 kW at 500 V AC 50/60 Hz (AC-3) 220 kW at 690 V AC 50/60 Hz (AC-3) 185 kW at 1000 V AC 50/60 Hz (AC-3) 90 kW at 230 V AC 50/60 Hz (AC-4) 160 kW at 400 V AC 50/60 Hz (AC-4) 160 kW at 415 V AC 50/60 Hz (AC-4) 185 kW at 440 V AC 50/60 Hz (AC-4) 200 kW at 500 V AC 50/60 Hz (AC-4) 220 kW at 690 V AC 50/60 Hz (AC-4) 185 kW at 1000 V AC 50/60 Hz (AC-4) |
Maximum Horse Power Rating | 100 hp at 200/208 V 60 Hz 125 hp at 230/240 V 60 Hz 250 hp at 460/480 V 60 Hz 300 hp at 575/600 V 60 Hz |
Irms rated making capacity | 3830 A at 440 V |
Coil technology | Built-in bidirectional peak limiting |
Safety reliability level | B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1 B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Mechanical durability | 8 Mcycles |
inrush power in VA (50/60 Hz, AC) | 700 VA |
inrush power in W (DC) | 645 W |
hold-in power consumption in VA (50/60 Hz, AC) | 15.0 VA |
hold-in power consumption in W (DC) | 9.1 W |
Operating time | 40…70 ms closing 15…50 ms opening |
Maximum operating rate | 600 cyc/h AC-3 600 cyc/h AC-3e 300 cyc/h AC-1 150 cyc/h AC-4 |
Connections – terminals | Power circuit: bar 2 – busbar cross section: 32 x 10 mm Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit: bolted connection Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) – cable stiffness: solid stranded without cable end Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) – cable stiffness: flexible with cable end Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) – cable stiffness: solid stranded without cable end Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) – cable stiffness: flexible with cable end |
Connection pitch | 1.8 in (45 mm) |
Mounting Support | Plate |
Standards | EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 |
Product Certifications | CB Scheme CCC cULus EAC CE UKCA EU-RO-MR by DNV-GL |
Tightening torque | 309.8 lbf.in (35 N.m) |
Height | 8.9 in (225 mm) |
Width | 5.5 in (140 mm) |
Depth | 8.9 in (226 mm) |
Net Weight | 16.5 lb(US) (7.5 kg) |
IP degree of protection | IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106 |
---|---|
Ambient Air Temperature for Operation | -13.0000000000…140.0000000000 °F (-25…60 °C) |
Ambient Air Temperature for Storage | -76.0000000000…176.0000000000 °F (-60…80 °C) |
Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open Vibrations 5…300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed |
color | Dark grey |
Protective treatment | TH |
Permissible ambient air temperature around the device | -40.0000000000…158.0000000000 °F (-40…70 °C) at Uc |
Category | US10I1222329 |
---|---|
Discount Schedule | 0I12 |
GTIN | 3606481921970 |
Returnability | Yes |
Country of origin | US |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 12.2 in (31.0 cm) |
Package 1 Width | 8.9 in (22.5 cm) |
Package 1 Length | 12.2 in (31.0 cm) |
Package 1 Weight | 16.475 lb(US) (7.473 kg) |
Unit Type of Package 2 | S06 |
Number of Units in Package 2 | 4 |
Package 2 Height | 41.3 in (105 cm) |
Package 2 Width | 23.6 in (60 cm) |
Package 2 Length | 31.5 in (80 cm) |
Package 2 Weight | 89.3 lb(US) (40.5 kg) |
There are no reviews yet.