LP1K1210BD is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 24V DC coil and 1NO auxiliary contact allowing easy integration to all control systems. LP1K1210BD is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 5.5kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it can be easily integrated into all control systems thanks to its 24V DC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Ready for connection to all control systems thanks to a 24V DC control voltage and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).

SKU: LP1K1210BD

Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 12A, 1 NO aux, 24VDC coil

LP1K1210BD

Main
Range TeSys
Product or Component Type Contactor
Device short name LP1K
contactor application Resistive load
Motor control
Complementary
Utilisation category AC-3
AC-3e
AC-1
AC-4
poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage Power circuit <= 690 V AC <= 400 Hz
Signalling circuit <= 690 V AC <= 400 Hz
[Ie] rated operational current 12 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
12 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
20 A (at <140.0000000000 °F (60 °C)) at <= 690 V AC AC-1 for power circuit
Control circuit type DC standard
[Uc] control circuit voltage 24 V DC
Motor power kW 3 kW 220…230 V AC 50/60 Hz AC-3
5.5 kW 380…415 V AC 50/60 Hz AC-3
5.5 kW 440 V AC 50/60 Hz AC-3
4 kW 690 V AC 50/60 Hz AC-3
3 kW 220…230 V AC 50/60 Hz AC-3e
5.5 kW 380…415 V AC 50/60 Hz AC-3e
5.5 kW 440 V AC 50/60 Hz AC-3e
4 kW 690 V AC 50/60 Hz AC-3e
3 kW 220…230 V AC 50/60 Hz AC-4
5.5 kW 380…415 V AC 50/60 Hz AC-4
5.5 kW 440 V AC 50/60 Hz AC-4
Auxiliary contact composition 1 NO
[Uimp] rated impulse withstand voltage 8 kV
Overvoltage category III
[Ith] conventional free air thermal current 20 A (at 140.0000000000 °F (60 °C)) for power circuit
10 A (at 122.0000000000 °F (50 °C)) for signalling circuit
Irms rated making capacity 144 A AC for power circuit conforming to IEC 60947
110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity 110 A at 440 V conforming to IEC 60947
80 A at 500 V conforming to IEC 60947
70 A at 660…690 V conforming to IEC 60947
[Icw] rated short-time withstand current 115 A 122.0000000000 °F (50 °C) – 1 s for power circuit
105 A 122.0000000000 °F (50 °C) – 5 s for power circuit
100 A 122.0000000000 °F (50 °C) – 10 s for power circuit
75 A 122.0000000000 °F (50 °C) – 30 s for power circuit
55 A 122.0000000000 °F (50 °C) – 1 min for power circuit
50 A 122.0000000000 °F (50 °C) – 3 min for power circuit
25 A 122.0000000000 °F (50 °C) – >= 15 min for power circuit
80 A – 1 s for signalling circuit
90 A – 500 ms for signalling circuit
110 A – 100 ms for signalling circuit
Associated fuse rating 25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660
Average impedance 3 mOhm – Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltage Power circuit 600 V UL 508
Power circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-5-1
Signalling circuit 600 V UL 508
Power circuit 600 V CSA C22.2 No 14
Signalling circuit 600 V CSA C22.2 No 14
Insulation resistance > 10 MOhm for signalling circuit
Inrush power in W 3 W 68.0000000000 °F (20 °C))
Hold-in power consumption in W 3 W 68.0000000000 °F (20 °C)
Heat dissipation 1.3 W
Control circuit voltage limits Operational: 0.8…1.15 Uc (at <122.0000000000 °F (50 °C))
Drop-out: >= 0.10 Uc (at <122.0000000000 °F (50 °C))
Connections – terminals screw clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid
screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end
screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid
screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end
screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end
Power circuit screw clamp terminals 2 0.002 in² (1.5 mm²)flexible with cable end
Maximum operating rate 3600 cyc/h
Auxiliary contacts type Instantaneous 1 NO
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Mounting Support Plate
Rail
Tightening torque 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals Philips No 2
7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals flat Ø 6 mm
7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals pozidriv No 2
Operating time 30…40 ms coil energisation and NO closing
10 ms coil de-energisation and NO opening
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 10 Mcycles
Electrical durability 1.3 Mcycles 12 A AC-3 <= 440 V
1.3 Mcycles 12 A AC-3e <= 440 V
0.3 Mcycles 20 A AC-1 <= 690 V
0.02 Mcycles 72 A AC-4 <= 440 V
Height 2.3 in (58 mm)
Width 1.8 in (45 mm)
Depth 2.2 in (57 mm)
Net Weight 0.496 lb(US) (0.225 kg)
Environment
Standards EN/IEC 60947-4-1
EN/IEC 60947-5-1
UL 60947-4-1
UL 60947-5-1
CSA C22.2 No 60947-4-1
CSA C22.2 No 60947-5-1
GB/T 14048.4
Product Certifications CB Scheme
CCC
UL
CSA
EAC
CE
UKCA
IP degree of protection IP2X
Ambient air temperature for operation -13.0000000000…122.0000000000 °F (-25…50 °C)
Ambient Air Temperature for Storage -58.0000000000…176.0000000000 °F (-50…80 °C)
Permissible ambient air temperature around the device -40.0000000000…158.0000000000 °F (-40…70 °C) at Uc
Operating altitude 6561.68 ft (2000 m) without derating
Flame retardance V1 conforming to UL 94
Requirement 2 conforming to NF F 16-101
Requirement 2 conforming to NF F 16-102
Ordering and shipping details
Category US10I1222321
Discount Schedule 0I12
GTIN 3389110790849
Returnability Yes
Country of origin FR
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 1.969 in (5.000 cm)
Package 1 Width 2.362 in (6.000 cm)
Package 1 Length 2.559 in (6.500 cm)
Package 1 Weight 7.866 oz (223.000 g)
Unit Type of Package 2 S02
Number of Units in Package 2 40
Package 2 Height 5.906 in (15.000 cm)
Package 2 Width 11.811 in (30.000 cm)
Package 2 Length 15.748 in (40.000 cm)
Package 2 Weight 20.344 lb(US) (9.228 kg)
Unit Type of Package 3 P06
Number of Units in Package 3 640
Package 3 Height 29.528 in (75.000 cm)
Package 3 Width 23.622 in (60.000 cm)
Package 3 Length 31.496 in (80.000 cm)
Package 3 Weight 340.641 lb(US) (154.512 kg)
Contractual warranty
Warranty 18 months
Peso 0.223 kg
Dimensiones 6 × 6.5 × 5 cm
Marcas

Schneider Electric

Marca

Schneider Electric

Product Datasheet
Instruction Sheet
Catalog
Environmental Disclosure

Customers reviews

There are no reviews yet.

Be the first to review “LP1K1210BD, Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 12A, 1 NO aux, 24VDC coil”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

Search for products

Back to Top
Elegir Moneda
USD Dólar de los Estados Unidos (US)
Product has been added to your cart